Fume Hood Testing Requirements: ANSI/ASHRAE 110 and Face Velocity
A chemical fume hood is the primary engineering control protecting lab employees from inhaling whatever is on the bench.
A chemical fume hood is the primary engineering control protecting lab employees from inhaling whatever is on the bench. When it works, it pulls contaminated air away from the user, up through the duct, and out of the building. When it doesn’t, the people in front of it are breathing what they are working with. That’s why Cal/OSHA’s Laboratory Standard treats fume hood performance as a measurable, documentable part of the Chemical Hygiene Plan, not a once-installed-and-forgotten piece of equipment.
This page covers what fume hood testing actually involves: the ANSI/ASHRAE Standard 110 methodology, how face velocity is measured, what counts as acceptable performance, and when a California lab needs the test performed. For a full overview of the written program a lab also needs, see our Chemical Hygiene Plan services for California labs guide.

What Fume Hood Testing Is and Why It Exists
Fume hood testing measures whether a hood is doing its job: capturing contaminants at the face of the hood, containing them inside, and venting them safely. Both the Cal/OSHA Laboratory Standard (8 CCR 5191) and the federal Laboratory Standard (29 CFR 1910.1450) require employers to make sure laboratory ventilation performs adequately for the chemicals in use. The plan must address it. The hood must back it up.
ANSI/ASHRAE Standard 110 is the recognized industry method for performance testing of laboratory fume hoods. The standard pairs three measurements:
- Face velocity testing. Measures the speed of air being drawn into the hood at the sash opening, in feet per minute (fpm). This is the indicator most people associate with hood testing.
- Smoke visualization. Confirms that the airflow at the face is actually flowing inward and that there are no reverse flows, swirls, or dead zones near the work surface.
- Tracer gas containment. Quantifies how much material would escape from inside the hood under a controlled release, measured at a mannequin breathing zone in front of the sash.
Face velocity is the routine, repeatable metric most labs track on a recurring basis. Smoke and tracer gas tests are usually performed at commissioning, after major repairs, or when a hood’s performance is in question.
How the Test Is Performed: Grid Sampling Across the Sash
Face velocity is not a single number you read off a meter. A hood’s airflow varies across the opening, and a test that measures only one point will miss low-flow areas where containment fails. The ANSI/ASHRAE 110 method addresses this by sampling the entire sash opening on a grid, at multiple sash positions, and averaging the results.
A qualified fume hood testing provider’s field procedure typically follows these steps:
Divide the sash opening into a grid of one-square-foot sections.
Each grid section is treated as a separate measurement location.
Take 20 timed samples at each grid location.
The samples are averaged at each point so a single anomalous reading does not skew the result.
Repeat the grid at three sash positions.
The hood is measured at full sash, 50% sash, and 25% sash. A hood that performs at one sash height can fail at another, and the people using it work at different sash heights throughout the day.
Calculate the average face velocity at each sash position.
The grid averages are rolled up into an overall face velocity for that sash height. Any individual low points are flagged.
Compare results to the acceptance threshold.
The lowest acceptable face velocity is tied to what the hood is used for, including whether the user works with carcinogens or other particularly hazardous substances under 8 CCR 5191 / 29 CFR 1910.1450.
Document the test.
Date, hood location, sash positions tested, grid readings, average and minimum velocities, smoke observations, and pass/fail status against the threshold. This is what the inspector wants to see.
The reason for the grid and the three sash positions is operational. A hood that averages 100 fpm overall can still have a corner reading 40 fpm, and that corner is where containment breaks down. The grid finds the corner. A single-point check does not.
What “Acceptable Performance” Means
Cal/OSHA does not publish one face velocity number that every hood must hit. The acceptance threshold depends on what the hood is used for. A hood used with low-hazard reagents has a different acceptable range than a hood used with carcinogens, reproductive toxins, or acutely toxic chemicals. The Laboratory Standard makes the employer responsible for matching ventilation performance to the hazards of the chemicals in use, and the Chemical Hygiene Plan must document how that determination was made.
In practice, that means the test report needs three things:
- The measured average and minimum face velocities at each sash position.
- The intended use of the hood, including whether particularly hazardous substances are used inside it.
- The acceptance threshold the hood is being measured against, and whether the hood passed or failed.
A hood that passes for general lab reagent use can fail the same day if the lab decides to start running a carcinogen inside it without raising the threshold. The plan and the test report have to stay aligned with what is actually happening at the bench.
When a California Lab Needs Fume Hood Testing
The Cal/OSHA Laboratory Standard requires lab ventilation to perform adequately for the chemicals in use, and the Chemical Hygiene Plan must address how that is confirmed. In practice, hoods get tested:
- At commissioning. Before the hood is put into service, to establish baseline performance and document acceptance.
- On a recurring schedule. Annual face velocity testing is the standard cadence at most California labs. Some sites test more frequently for hoods handling particularly hazardous substances.
- After any change that affects airflow. A new building HVAC balance, a duct or fan repair, a hood relocation, an added makeup-air unit, a sash that has been adjusted or replaced. All of these can shift performance.
- After a near-miss or symptom report. If an employee reports an odor at the face of the hood, a visible reverse flow, or a chemical exposure that should have been contained, the hood gets retested before it goes back into service.
- Before a Cal/OSHA visit. Inspectors often ask for current fume hood test reports. A plan that names a fume hood but has no recent test documenting it works is a deficiency.
When creating or revising a Chemical Hygiene Plan, current fume hood records are important inputs. A common gap is not proof that a hood is broken, but the absence of a documented test or reliance on a report that predates a change in the chemicals being used.
How Fume Hood Testing Fits Into a Chemical Hygiene Plan
CDMS does not perform ANSI/ASHRAE Standard 110 face-velocity testing, standalone testing, equipment certification, or hood repair. Your facility must arrange those services with a qualified fume hood testing provider and retain the resulting report with the Chemical Hygiene Plan.
CDMS’s role is limited to creating or revising the CHP and delivering the training tied to it. The plan should identify the hoods in use, the operating practices employees must follow, where current performance records are kept, and who is responsible for arranging future testing. If a qualified provider’s report changes how a hood may be used, the employer should update the CHP and retrain affected employees.
Trusted throughout California
BSY started working with CDMS last year after our in-house EHS person departed the company. CDMS reviewed our existing operational permits as well as any additional Federal, State and Local regulations that could apply and helped us to create a comprehensive compliance calendar to track regulatory deadlines and submittal due dates. The CDMS team does an excellent job of tracking everything and can be relied upon to complete the forms accurately and assist with submittals, allowing me to focus on our business.
Speak with a CDMS EHS expert
Tell us about your facility and your deadline. You’ll get a clear read on what applies and a scoped plan to handle it.












